Ready to Proceed?
Request a Firm Quotation for 40 MVA 66kV/11kV Three-Phase Oil-Immersed...
Share your project specifications and receive an official CIF quotation within 24 hours.
This 40 MVA / three-phase oil-immersed power transformer is designed for utility substation, grid interconnection, and large industrial applications. Suitable for transmission and sub-transmission voltage classes. IEC 60076 design reference; ONAN/ONAF cooling options available. Manufactured and exported from Hefei, China.
| Rated Capacity | 40 MVA (40,000 kVA) |
|---|---|
| High Voltage | 66.0 kV |
| Low Voltage | 11.0 kV / customized |
| Frequency | 50 Hz / 60 Hz |
| Phase | Three Phase |
| Cooling Method | ONAN / ONAF optional |
| Vector Group | YNd11 / YNyn0 / customized |
| Tap Changer | On-load tap changer (OLTC) / Off-circuit optional |
| Tapping Range | +/-8 x 1.25% (OLTC) / +/-2 x 2.5% (OCTC) |
| Winding Material | Copper |
| Core Material | CRGO silicon steel, grain-oriented |
| Insulation Medium | Mineral insulating oil |
| Standard | IEC 60076 design reference |
| Installation | Outdoor substation / indoor GIS substation |
Official XinHuan factory 2D vector General Arrangement drawing for 40 MVA 66kV/11kV Three-Phase Oil-Immersed Power Transformer. Includes front elevation view, top plan view, terminal centerline clearances, base channel mounting footprint, and complete vector group connection schematics.
Built with tier-1 certified raw materials engineered for long operational life (>30 years), superior dielectric withstand, and high short-circuit withstand capacity.
High-grade grain-oriented cold-rolled silicon steel with step-lap mitered joints for low $P_o$ losses.
Electrolytic oxygen-free copper with high thermal grade insulation for surge resistance.
De-energized tap switch ($\pm 2 \times 2.5\%$) or on-load vacuum tap changer (OLTC) optional.
Buchholz gas relay, magnetic oil gauge (MOG), and dial thermometers with alarm contacts.
Every transformer unit manufactured by XinHuan undergoes mandatory routine factory testing prior to container dispatch. Full certified routine and type test submittal reports are provided with commercial documentation:
Megger test (HV to LV, HV to Earth, LV to Earth) >1000 MΩ.
Turns ratio check across all taps with phase displacement check.
Precision Kelvin bridge measurement across all tap positions.
Load loss ($P_k$) measurement corrected to reference temp (75°C).
Core excitation test ($P_o$ and $I_o$) at rated sinusoidal voltage.
Power-frequency separate source test (e.g. 50kV/70kV 1 min).
Full wave & chopped wave impulse withstand (BIL up to 170kV).
Ultra-low discharge (<5 pC) and pressurized oil/gas tightness test.
Large power transformers are shipped with oil-filled or oil-free transport options depending on voltage class and destination. All units include full documentation: routine test report, nameplate data, packing list, and certificate of origin. Lead time is confirmed at order stage based on specification complexity.
Standard manufacturing cycle is 4 to 6 weeks from approval of GA blueprints and single-line diagrams.
Vacuum moisture barrier preservation, nitrogen blanketing, and reinforced steel-frame structural crate skids.
Fast ocean freight to Port of Chancay & Callao (25-35 days), Manila, Lagos, and Middle East ports.
Watch XinHuan technicians perform routine dielectric testing, winding insulation checks, and quality inspections inside our Hefei manufacturing plant.
Send your single-line diagram (SLD), voltage ratings, or tender specifications. Our chief electrical engineers will review and issue an actionable CIF quotation within 24 hours.
Frequently asked questions regarding specifications, certifications, and delivery for 40 MVA 66kV/11kV Three-Phase Oil-Immersed Power Transformer.
Ready to Proceed?
Share your project specifications and receive an official CIF quotation within 24 hours.