Need a FAT-Supported Transformer?
Request a Quote — FAT Included on Request
Include your test requirements in the RFQ. We confirm which routine and type tests are available, and coordinate third-party inspection if required.
Quality Assurance Guide
A factory acceptance test is a witnessed routine test at the manufacturer's facility before shipment. Buyers who insist on FAT catch non-conformances before the transformer reaches site — where corrections are far more costly and time-consuming.
These three terms are often confused. Understanding the distinction helps you specify what you need in your purchase order.
| Test category | Performed on | Purpose | Buyer present? |
|---|---|---|---|
| Routine test | Every unit produced | Verify the individual transformer meets rated parameters | No — internal quality control |
| Type test | One unit per design | Prove the design meets standard under extreme conditions (temperature rise, impulse, short-circuit) | Optional — done once per design family |
| FAT | Every unit (when specified) | Witnessed routine test: buyer or inspector verifies results before shipment | Yes — this is the definition of FAT |
Cross-check the nameplate data against your purchase order line by line:
DC resistance of each winding measured at each tap position. Used to verify conductor continuity and detect shorted or open turns. Results corrected to reference temperature (75°C per IEC, 85°C per ANSI). Values should be balanced between phases (typically within ±0.5%).
Actual voltage ratio measured and compared to nameplate ratio at each tap. The measured ratio should agree with the specified turns ratio to within ±0.5% (IEC) at each tap position. Verifies that the tap changer is correctly connected and the turns count is correct.
Confirms that the relative phase angle between HV and LV windings matches the declared vector group (e.g. Dyn11 = 30° displacement). Critical for parallel operation and protection relay coordination.
The short-circuit (load) loss and leakage impedance measured at rated current, corrected to reference temperature. Load loss (Pk) determines the transformer's copper loss at full load — confirm it does not exceed the guaranteed value in your specification. Impedance % affects fault current levels.
Core loss measured at rated voltage and frequency, with no load connected. No-load loss is present 24/7 whenever the transformer is energised. Verify that P0 does not exceed the guaranteed value. No-load current (excitation current) should also be within specified limits. These values can be entered directly into the Loss Calculator.
Megohm test applied between each winding and earth (and between windings). Higher resistance is better. The polarisation index (PI = IR at 10 min / IR at 1 min) indicates insulation condition — a PI below 1.0 on a new transformer is cause for concern. Minimum acceptable values depend on voltage class.
Elevated AC voltage applied between each winding and earthed tank for 60 seconds. The test voltage level is defined by the voltage class and insulation level in the standard. No breakdown or flashover is acceptable.
The LV winding is energised at double rated voltage (using twice the rated frequency to avoid core saturation). Verifies the inter-winding and inter-turn insulation can withstand temporary overvoltages.
Oil sample taken from the transformer and tested for breakdown voltage (BDV). IEC 60156 specifies the test procedure. BDV should be ≥60 kV (IEC, for 170 kV class and below at 2.5 mm gap). Lower values indicate moisture or contamination in the oil.
Gas-in-oil analysis detects combustible gases (H₂, CH₄, C₂H₂, CO, etc.) that are produced by thermal and electrical faults inside the transformer. A baseline DGA on new oil before shipment is useful for comparison during service life. Not a routine test — request it specifically.
Before approving shipment, confirm you have received — or will receive with the shipment — the following:
If you cannot send your own engineer to China for the FAT, a third-party inspection agency can attend on your behalf. The three most widely used for transformer FAT in China are:
Global testing and inspection group. Can arrange inspectors at transformer factories throughout China. Provides independent test witnessing reports accepted by most utility and EPC clients.
International classification and testing body. BV inspection reports are widely recognised by African, Middle East, and European utilities. BV China offices cover major manufacturing cities.
Global quality and safety testing organisation. Widely used by North American buyers sourcing from China. Can also issue ETL marks for ANSI-market transformers where required.
To arrange third-party inspection: contact the agency directly with the factory location and test date. Alternatively, ask the transformer manufacturer — most established factories are accustomed to hosting SGS, BV, or Intertek inspectors and can coordinate the schedule.
The no-load loss (P0) and load loss (Pk) values from the routine test report are the most accurate inputs for energy cost modelling. Enter them directly into the Transformer Loss Calculator to compare the actual tested unit against your specification guarantee or a competing offer.
Open Loss CalculatorXinHuan supports factory acceptance testing for all orders. Tell us your test requirements in the RFQ.
Request a Quote Ask About FAT ArrangementsTransformer Academy
Start with the plain-English basics, then move into RFQ, testing, standards, cooling, and calculator tools.
Need a FAT-Supported Transformer?
Include your test requirements in the RFQ. We confirm which routine and type tests are available, and coordinate third-party inspection if required.