Ready to Proceed?
Request a Firm Quotation for 100 kVA 11kV/480V Three-Phase Dry...
Share your project specifications and receive an official CIF quotation within 24 hours.
This 100 kva /480v three-phase dry distribution transformer is designed for indoor power distribution where safety, low maintenance, and practical insulation performance are important. It provides dependable service for commercial, industrial, infrastructure, or special-application installations and can be customized according to voltage, enclosure, cooling, and monitoring requirements.
| Model Series | SCB10 / SCB11 / SCB13 / SCB14 |
|---|---|
| Rated Capacity | 100 kVA |
| Primary Voltage (U1) | 10,000 V (10 kV / 11 kV) |
| Secondary Voltage (U2) | 400 V / 415 V / 480 V (3-Phase 4-Wire) |
| Vector Group | Dyn11 |
| Rated Frequency | 50 Hz / 60 Hz |
| Cooling Method | AN (Natural Air) / AF (Forced Air Blower) |
| Primary Current (I1) | 5.77 A |
| Secondary Current (I2) | 139.1 A |
| Guaranteed No-Load Loss (P0) | 400 W |
| Guaranteed Load Loss (Pk at 120°C) | 1570 W |
| Short-Circuit Impedance (Uk) | 4.0% |
| Insulation Class | F Class (155°C) / H Class (180°C) Epoxy Cast Resin |
| Temperature Rise Limit | Winding Temp Rise ≤ 100 K (F Class) / ≤ 125 K (H Class) |
| IP Protection Class | IP00 (Open Type) / IP20 (Indoor Enclosure) / IP23 (Loubered) |
| Total Weight | 750 kg |
| Overall Footprint (L×W×H) | 900 mm × 650 mm × 950 mm |
| Governing Standards | IEC 60076-11, GB/T 10228-2015, CE, ISO 9001 |
Official XinHuan factory 2D vector General Arrangement drawing for 100 kVA 11kV/480V Three-Phase Dry Distribution Transformer. Includes front elevation view, top plan view, terminal centerline clearances, base channel mounting footprint, and complete vector group connection schematics.
Built with tier-1 certified raw materials engineered for long operational life (>30 years), superior dielectric withstand, and high short-circuit withstand capacity.
High-grade grain-oriented cold-rolled silicon steel with step-lap mitered joints for low $P_o$ losses.
Electrolytic oxygen-free copper with high thermal grade insulation for surge resistance.
De-energized tap switch ($\pm 2 \times 2.5\%$) or on-load vacuum tap changer (OLTC) optional.
Buchholz gas relay, magnetic oil gauge (MOG), and dial thermometers with alarm contacts.
Every transformer unit manufactured by XinHuan undergoes mandatory routine factory testing prior to container dispatch. Full certified routine and type test submittal reports are provided with commercial documentation:
Megger test (HV to LV, HV to Earth, LV to Earth) >1000 MΩ.
Turns ratio check across all taps with phase displacement check.
Precision Kelvin bridge measurement across all tap positions.
Load loss ($P_k$) measurement corrected to reference temp (75°C).
Core excitation test ($P_o$ and $I_o$) at rated sinusoidal voltage.
Power-frequency separate source test (e.g. 50kV/70kV 1 min).
Full wave & chopped wave impulse withstand (BIL up to 170kV).
Ultra-low discharge (<5 pC) and pressurized oil/gas tightness test.
The product is prepared for export shipment with suitable packing and transport arrangements based on destination and handling requirements. Technical documents, test reports, nameplate confirmation, and pre-shipment support can be supplied according to order requirements. OEM/ODM support and project-based coordination are available for qualified inquiries.
Standard manufacturing cycle is 4 to 6 weeks from approval of GA blueprints and single-line diagrams.
Vacuum moisture barrier preservation, nitrogen blanketing, and reinforced steel-frame structural crate skids.
Fast ocean freight to Port of Chancay & Callao (25-35 days), Manila, Lagos, and Middle East ports.
Watch XinHuan technicians perform routine dielectric testing, winding insulation checks, and quality inspections inside our Hefei manufacturing plant.
Send your single-line diagram (SLD), voltage ratings, or tender specifications. Our chief electrical engineers will review and issue an actionable CIF quotation within 24 hours.
Frequently asked questions regarding specifications, certifications, and delivery for 100 kVA 11kV/480V Three-Phase Dry Distribution Transformer.
Ready to Proceed?
Share your project specifications and receive an official CIF quotation within 24 hours.