Ready to Proceed?
Request a Firm Quotation for 400 kVA 33kV Three-Phase Oil-Immersed...
Share your project specifications and receive an official CIF quotation within 24 hours.
This 400 kVA oil-immersed distribution transformer is designed for reliable power distribution in rural utility networks, industrial feeders, and infrastructure projects across Africa, MENA, and other grid markets. ONAN cooling with IEC 60076 design reference. Export-ready from Hefei, China.
| Rated Capacity | 400 kVA |
|---|---|
| Primary Voltage (U1) | 33,000 V (33 kV) |
| Secondary Voltage (U2) | 415 V / 240 V (3-Phase 4-Wire) |
| Vector Group | Dyn11 |
| Rated Frequency | 50 Hz |
| Cooling Method | ONAN (Oil Natural Air Natural) |
| Primary Current (I1) | 7.0 A |
| Secondary Current (I2) | 556.5 A |
| Guaranteed No-Load Loss (P0) | 570 W |
| Guaranteed Load Loss (Pk at 75°C) | 3900 W |
| Short-Circuit Impedance (Uk) | 4.0% |
| HV Insulation Level | LI 170 / AC 70 (33kV Class) |
| Temperature Rise Limits | Top Oil ≤ 50K, Winding ≤ 55K (45°C Ambient) |
| Creepage Distance | ≥ 31 mm/kV (Outdoor Tropicalized Porcelain) |
| Core & Coil Weight | 780 kg |
| Insulating Oil Weight | 490 kg |
| Total Assembled Weight | 1550 kg |
| Overall Footprint (L×W×H) | 1320 mm × 880 mm × 1480 mm |
| Governing Standards | IEC 60076, BS 171, SON NIS, NERC Code |
Official XinHuan factory 2D vector General Arrangement drawing for 400 kVA 33kV Three-Phase Oil-Immersed Distribution Transformer. Includes front elevation view, top plan view, terminal centerline clearances, base channel mounting footprint, and complete vector group connection schematics.
Built with tier-1 certified raw materials engineered for long operational life (>30 years), superior dielectric withstand, and high short-circuit withstand capacity.
High-grade grain-oriented cold-rolled silicon steel with step-lap mitered joints for low $P_o$ losses.
Electrolytic oxygen-free copper with high thermal grade insulation for surge resistance.
De-energized tap switch ($\pm 2 \times 2.5\%$) or on-load vacuum tap changer (OLTC) optional.
Buchholz gas relay, magnetic oil gauge (MOG), and dial thermometers with alarm contacts.
Every transformer unit manufactured by XinHuan undergoes mandatory routine factory testing prior to container dispatch. Full certified routine and type test submittal reports are provided with commercial documentation:
Megger test (HV to LV, HV to Earth, LV to Earth) >1000 MΩ.
Turns ratio check across all taps with phase displacement check.
Precision Kelvin bridge measurement across all tap positions.
Load loss ($P_k$) measurement corrected to reference temp (75°C).
Core excitation test ($P_o$ and $I_o$) at rated sinusoidal voltage.
Power-frequency separate source test (e.g. 50kV/70kV 1 min).
Full wave & chopped wave impulse withstand (BIL up to 170kV).
Ultra-low discharge (<5 pC) and pressurized oil/gas tightness test.
The product is prepared for export shipment with suitable packing and transport arrangements based on destination and handling requirements. Sea freight, air freight, and land transport options are available. Lead time is project-dependent and confirmed at order stage.
Standard manufacturing cycle is 4 to 6 weeks from approval of GA blueprints and single-line diagrams.
Vacuum moisture barrier preservation, nitrogen blanketing, and reinforced steel-frame structural crate skids.
Fast ocean freight to Port of Chancay & Callao (25-35 days), Manila, Lagos, and Middle East ports.
Watch XinHuan technicians perform routine dielectric testing, winding insulation checks, and quality inspections inside our Hefei manufacturing plant.
Send your single-line diagram (SLD), voltage ratings, or tender specifications. Our chief electrical engineers will review and issue an actionable CIF quotation within 24 hours.
Frequently asked questions regarding specifications, certifications, and delivery for 400 kVA 33kV Three-Phase Oil-Immersed Distribution Transformer.
Ready to Proceed?
Share your project specifications and receive an official CIF quotation within 24 hours.