Ref: XH-SUB-2026-0527
XINHUAN Submittal Package
Anhui XinHuan Electrical Power Equipment Co., Ltd. | Hefei Manufacturing Base
CNAS Test Certified | ISO 9001:2015 | ISO 14001:2015 Registered OEM
SUBMITTAL REF: XH-SUB-2026-0527
Date: 2026-10-30
Standard: IEC 60076 / GB/T 1094 / ANSI C57
Compact Substations

75 kVA 13.8kV Three-Phase Pad-Mounted Transformer (480Y/277V Radial Feed)

Submittal Specification Datasheet & Engineering Technical Parameters

1. Electrical Technical Parameters & Ratings

Full parameter ratings configured per client submittal order requirements.

Transient Simulation & Saturation Characteristics (PSCAD / ETAP / EMTP)

IEEE C57.12.00 / IEC 60076-1
Electromagnetic Parameter Design Characteristic & Certified Benchmark Grid Study Application
Saturation Knee-Point Voltage (\(V_k\)) 1.15 ~ 1.22 p.u. of \(V_n\) (CRGO Laser Core) Overvoltage & Ferroresonance Protection
Air-Core Reactance (\(X_{\text{air}}\)) \(2.0 \sim 2.5 \times X_{sc}\) (Standard: \(2.1 \times X_{sc}\)) Deep Saturation Inrush Peak Limit
Air-Core Inductance (\(L_{\text{air}}\)) \(L_{\text{air}} = X_{\text{air}} / (2\pi f)\) (Winding Specific) PSCAD Saturable Core / UMEC Modeling
Inrush Current Ratio (\(I_{\text{inrush}} / I_n\)) 8.0 ~ 12.0 × Rated \(I_n\) (Decay \(\tau \approx 0.15\text{s} \sim 0.35\text{s}\)) Protective Relay Coordination & POI Voltage Dip
Magnetizing Inrush Decay Constant (\(\tau\)) \(\tau = L_{\text{air}} / R_w\) (Typically 100 ms – 350 ms) Differential Relay (87T) Harmonic Restraint
Need project-specific \(V\text{-}I\) curve or PSCAD `.csv` dataset for renewable grid interconnection? Interactive V-I Calculator

2. 2D AutoCAD General Arrangement (GA) Drawing & Dimensional Profile

XinHuan Pad-Mounted Substation 2D AutoCAD Blueprint
Figure 2.1 — 2D AutoCAD Dimensional Submittal Schematic

Dimensional & Installation Requirements

  • Foundational Base: Concrete pad mounting with perimeter sill channel anchoring.
  • Bushings Orientation: Dead-front HV wells (loop/radial) & LV NEMA copper spade terminals.
  • Grounding Terminals: Dual M12 copper ground pads in HV & LV compartments.
  • Enclosure Protection: ANSI C57.12.28 tamper-resistant powder-coated Munsell Green.
  • CAD Drawing File: Request `.DXF` or `.DWG` blocks from sales engineering.

3. Factory Acceptance Testing (FAT) & Routine Test Protocol

Every pad-mounted transformer manufactured by XinHuan undergoes 100% routine inspection in accordance with ANSI C57.12.00 / C57.12.90 and IEEE C57.12.28 before dispatch. Routine test certificates are included in the shipment package.

1. Winding Resistance Measurement (HV & LV)
2. Voltage Ratio & Vector Group Phase Displacement
3. Short-Circuit Impedance & Load Loss Test
4. No-Load Loss ($P_o$) & Excitation Current Test
5. Separate-Source AC Dielectric Withstand Test
6. Induced Overvoltage Withstand Test (DVWV)
7. Insulation Resistance & Polarization Index (Megger)
8. Hermetic Tank Pressure Leakage & Oil BDV Test
9. Extended Excitation Characteristic & Knee-Point Verification (to 120% \(V_n\))
10. Frequency Response Analysis (FRA) & Air-Core Reactance Test (Optional)

4. Seaport Logistics, Packaging & Warranty Terms

Export Packaging
IPPC fumigated solid wooden crate skid with vacuum moisture foil barrier.
Primary Delivery Ports
CIF Chancay, Callao, Apapa, Mombasa, Manila, Jakarta, Santos, & Valparaiso.
Factory Warranty
36 Months Full Replacement / Factory Engineering Warranty against defects.
Anhui XinHuan Electrical Power Equipment Co., Ltd.
Factory Address: Industrial Park, Hefei City, Anhui Province, China | Export Dept: [email protected]
Submittal Document Code: XH-SUB-2026-0527 — Confidential Technical Datasheet