SUBMITTAL REF: XH-SUB-2026-0482
Date: 2026-10-30
Standard: IEC 60076 / GB/T 1094 / ANSI C57
Isolation Transformers

SG Three Phase Dry-Type Isolation Transformer (0.3 kVA – 180 kVA)

Submittal Specification Datasheet & Engineering Technical Parameters

1. Electrical Technical Parameters & Ratings

Parameter Specification Design Rating & Certified Value
Rated Capacity Range 0.3 kVA to 180 kVA (e.g. 5 kVA, 10 kVA, 50 kVA, 100 kVA)
Primary Input Voltage 220V, 230V, 380V, 400V, 415V, 440V, 480V, 660V (Customizable)
Secondary Output Voltage 200V, 220V, 380V, 400V, 415V, 110V (Customizable)
Target Philippine Spec 220V 3-Phase Input -> 380V 3-Phase Output, 5 kVA, 100% Copper Conductor
Rated Frequency 50 Hz / 60 Hz
Number of Phases Three Phase (3-Phase 3-Wire or 3-Phase 4-Wire with Neutral)
Conductor Material 100% Pure Oxygen-Free Copper (Cu)
Insulation Resistance ≥ 100 MΩ (DC 1000V)
Dielectric Strength 2500V AC / 1 min (No flashover or breakdown)
Efficiency ≥ 98.0%
Noise Level < 45 dB(A)
Temperature Rise < 80K (Class F) / < 100K (Class H)
Enclosure Protection IP00 (Open Type) / IP20 / IP54 (Ventilated Louver Cabinet)
Model SG-0.3/0.5KVA Bmax: 210 mm, Cmax: 230 mm, Dmax: 180 mm, Packing L: 210 mm, Packing W: 230 mm, Packing H: 180 mm
Model SG-0.75KVA Bmax: 250 mm, Cmax: 230 mm, Dmax: 180 mm, Packing L: 210 mm, Packing W: 230 mm, Packing H: 180 mm
Model SG-1KVA Bmax: 250 mm, Cmax: 300 mm, Dmax: 230 mm, Packing L: 310 mm, Packing W: 410 mm, Packing H: 285 mm
Model SG-1.5KVA Bmax: 280 mm, Cmax: 300 mm, Dmax: 230 mm, Packing L: 310 mm, Packing W: 410 mm, Packing H: 285 mm
Model SG-2~5KVA Bmax: 280 mm, Cmax: 400 mm, Dmax: 390 mm, Packing L: 310 mm, Packing W: 440 mm, Packing H: 490 mm
Model SG-6KVA Bmax: 320 mm, Cmax: 450 mm, Dmax: 460 mm, Packing L: 360 mm, Packing W: 490 mm, Packing H: 560 mm
Model SG-8~15KVA Bmax: 350 mm, Cmax: 500 mm, Dmax: 520 mm, Packing L: 380 mm, Packing W: 550 mm, Packing H: 650 mm
Model SG-20/25KVA Bmax: 400 mm, Cmax: 550 mm, Dmax: 570 mm, Packing L: 430 mm, Packing W: 600 mm, Packing H: 700 mm
Model SG-30KVA Bmax: 450 mm, Cmax: 600 mm, Dmax: 620 mm, Packing L: 380 mm, Packing W: 550 mm, Packing H: 650 mm
Model SG-35KVA Bmax: 450 mm, Cmax: 600 mm, Dmax: 620 mm, Packing L: 480 mm, Packing W: 640 mm, Packing H: 780 mm
Model SG-40KVA Bmax: 450 mm, Cmax: 600 mm, Dmax: 620 mm, Packing L: 380 mm, Packing W: 550 mm, Packing H: 650 mm
Model SG-50~70KVA Bmax: 750 mm, Cmax: 600 mm, Dmax: 750 mm, Packing L: 780 mm, Packing W: 640 mm, Packing H: 870 mm
Model SG-80~125KVA Bmax: 850 mm, Cmax: 650 mm, Dmax: 850 mm, Packing L: 880 mm, Packing W: 690 mm, Packing H: 1000 mm
Model SG-150/180KVA Bmax: 1000 mm, Cmax: 700 mm, Dmax: 950 mm, Packing L: 1040 mm, Packing W: 750 mm, Packing H: 1100 mm

Transient Simulation & Saturation Characteristics (PSCAD / ETAP / EMTP)

IEEE C57.12.00 / IEC 60076-1
Electromagnetic Parameter Design Characteristic & Certified Benchmark Grid Study Application
Saturation Knee-Point Voltage (\(V_k\)) 1.15 ~ 1.22 p.u. of \(V_n\) (CRGO Laser Core) Overvoltage & Ferroresonance Protection
Air-Core Reactance (\(X_{\text{air}}\)) \(2.0 \sim 2.5 \times X_{sc}\) (Standard: \(2.1 \times X_{sc}\)) Deep Saturation Inrush Peak Limit
Air-Core Inductance (\(L_{\text{air}}\)) \(L_{\text{air}} = X_{\text{air}} / (2\pi f)\) (Winding Specific) PSCAD Saturable Core / UMEC Modeling
Inrush Current Ratio (\(I_{\text{inrush}} / I_n\)) 8.0 ~ 12.0 × Rated \(I_n\) (Decay \(\tau \approx 0.15\text{s} \sim 0.35\text{s}\)) Protective Relay Coordination & POI Voltage Dip
Magnetizing Inrush Decay Constant (\(\tau\)) \(\tau = L_{\text{air}} / R_w\) (Typically 100 ms – 350 ms) Differential Relay (87T) Harmonic Restraint
Need project-specific \(V\text{-}I\) curve or PSCAD `.csv` dataset for renewable grid interconnection? Interactive V-I Calculator

2. 2D AutoCAD General Arrangement (GA) Drawing & Dimensional Profile

2D AutoCAD Blueprint
Figure 2.1 — 2D AutoCAD Dimensional Submittal Schematic

Dimensional & Installation Requirements

  • Foundational Base: Steel channel Skid / Sub-station Pad Mounting.
  • Bushings Orientation: HV top-mounted / side-cabinet entry option.
  • Grounding Terminals: Dual M12 copper grounding pads on diagonal corners.
  • Enclosure Protection: IP54 Outdoor Corrosive C4/C5 Marine Paint Coating.
  • CAD Drawing File: Request `.DXF` or `.DWG` blocks from sales engineering.

3. Factory Acceptance Testing (FAT) & Routine Test Protocol

Every transformer manufactured by XinHuan undergoes 100% routine inspection in accordance with IEC 60076-1 before dispatch. Routine test certificates are included in the shipment package.

1. Winding Resistance Measurement (HV & LV)
2. Voltage Ratio & Vector Group Phase Displacement
3. Short-Circuit Impedance & Load Loss Test
4. No-Load Loss ($P_o$) & Excitation Current Test
5. Separate-Source AC Dielectric Withstand Test
6. Induced Overvoltage Withstand Test (DVWV)
7. Insulation Resistance & Polarization Index (Megger)
8. Hermetic Tank Pressure Leakage & Oil BDV Test
9. Extended Excitation Characteristic & Knee-Point Verification (to 120% \(V_n\))
10. Frequency Response Analysis (FRA) & Air-Core Reactance Test (Optional)

4. Seaport Logistics, Packaging & Warranty Terms

Export Packaging
IPPC fumigated solid wooden crate skid with vacuum moisture foil barrier.
Primary Delivery Ports
CIF Chancay, Callao, Apapa, Mombasa, Manila, Jakarta, Santos, & Valparaiso.
Factory Warranty
36 Months Full Replacement / Factory Engineering Warranty against defects.
Anhui XinHuan Electrical Power Equipment Co., Ltd.
Factory Address: Industrial Park, Hefei City, Anhui Province, China | Export Dept: [email protected]
Submittal Document Code: XH-SUB-2026-0482 — Confidential Technical Datasheet