Ref: XH-SUB-2026-0482
XINHUAN
Submittal Package
Anhui XinHuan Electrical Power Equipment Co., Ltd. | Hefei Manufacturing Base
CNAS Test Certified | ISO 9001:2015 | ISO 14001:2015 Registered OEM
SUBMITTAL REF: XH-SUB-2026-0482
Date: 2026-10-30
Standard: IEC 60076 / GB/T 1094 / ANSI C57
Isolation Transformers
SG Three Phase Dry-Type Isolation Transformer (0.3 kVA – 180 kVA)
Submittal Specification Datasheet & Engineering Technical Parameters
1. Electrical Technical Parameters & Ratings
| Parameter Specification | Design Rating & Certified Value |
|---|---|
| Rated Capacity Range | 0.3 kVA to 180 kVA (e.g. 5 kVA, 10 kVA, 50 kVA, 100 kVA) |
| Primary Input Voltage | 220V, 230V, 380V, 400V, 415V, 440V, 480V, 660V (Customizable) |
| Secondary Output Voltage | 200V, 220V, 380V, 400V, 415V, 110V (Customizable) |
| Target Philippine Spec | 220V 3-Phase Input -> 380V 3-Phase Output, 5 kVA, 100% Copper Conductor |
| Rated Frequency | 50 Hz / 60 Hz |
| Number of Phases | Three Phase (3-Phase 3-Wire or 3-Phase 4-Wire with Neutral) |
| Conductor Material | 100% Pure Oxygen-Free Copper (Cu) |
| Insulation Resistance | ≥ 100 MΩ (DC 1000V) |
| Dielectric Strength | 2500V AC / 1 min (No flashover or breakdown) |
| Efficiency | ≥ 98.0% |
| Noise Level | < 45 dB(A) |
| Temperature Rise | < 80K (Class F) / < 100K (Class H) |
| Enclosure Protection | IP00 (Open Type) / IP20 / IP54 (Ventilated Louver Cabinet) |
| Model SG-0.3/0.5KVA | Bmax: 210 mm, Cmax: 230 mm, Dmax: 180 mm, Packing L: 210 mm, Packing W: 230 mm, Packing H: 180 mm |
| Model SG-0.75KVA | Bmax: 250 mm, Cmax: 230 mm, Dmax: 180 mm, Packing L: 210 mm, Packing W: 230 mm, Packing H: 180 mm |
| Model SG-1KVA | Bmax: 250 mm, Cmax: 300 mm, Dmax: 230 mm, Packing L: 310 mm, Packing W: 410 mm, Packing H: 285 mm |
| Model SG-1.5KVA | Bmax: 280 mm, Cmax: 300 mm, Dmax: 230 mm, Packing L: 310 mm, Packing W: 410 mm, Packing H: 285 mm |
| Model SG-2~5KVA | Bmax: 280 mm, Cmax: 400 mm, Dmax: 390 mm, Packing L: 310 mm, Packing W: 440 mm, Packing H: 490 mm |
| Model SG-6KVA | Bmax: 320 mm, Cmax: 450 mm, Dmax: 460 mm, Packing L: 360 mm, Packing W: 490 mm, Packing H: 560 mm |
| Model SG-8~15KVA | Bmax: 350 mm, Cmax: 500 mm, Dmax: 520 mm, Packing L: 380 mm, Packing W: 550 mm, Packing H: 650 mm |
| Model SG-20/25KVA | Bmax: 400 mm, Cmax: 550 mm, Dmax: 570 mm, Packing L: 430 mm, Packing W: 600 mm, Packing H: 700 mm |
| Model SG-30KVA | Bmax: 450 mm, Cmax: 600 mm, Dmax: 620 mm, Packing L: 380 mm, Packing W: 550 mm, Packing H: 650 mm |
| Model SG-35KVA | Bmax: 450 mm, Cmax: 600 mm, Dmax: 620 mm, Packing L: 480 mm, Packing W: 640 mm, Packing H: 780 mm |
| Model SG-40KVA | Bmax: 450 mm, Cmax: 600 mm, Dmax: 620 mm, Packing L: 380 mm, Packing W: 550 mm, Packing H: 650 mm |
| Model SG-50~70KVA | Bmax: 750 mm, Cmax: 600 mm, Dmax: 750 mm, Packing L: 780 mm, Packing W: 640 mm, Packing H: 870 mm |
| Model SG-80~125KVA | Bmax: 850 mm, Cmax: 650 mm, Dmax: 850 mm, Packing L: 880 mm, Packing W: 690 mm, Packing H: 1000 mm |
| Model SG-150/180KVA | Bmax: 1000 mm, Cmax: 700 mm, Dmax: 950 mm, Packing L: 1040 mm, Packing W: 750 mm, Packing H: 1100 mm |
Transient Simulation & Saturation Characteristics (PSCAD / ETAP / EMTP)
IEEE C57.12.00 / IEC 60076-1| Electromagnetic Parameter | Design Characteristic & Certified Benchmark | Grid Study Application |
|---|---|---|
| Saturation Knee-Point Voltage (\(V_k\)) | 1.15 ~ 1.22 p.u. of \(V_n\) (CRGO Laser Core) | Overvoltage & Ferroresonance Protection |
| Air-Core Reactance (\(X_{\text{air}}\)) | \(2.0 \sim 2.5 \times X_{sc}\) (Standard: \(2.1 \times X_{sc}\)) | Deep Saturation Inrush Peak Limit |
| Air-Core Inductance (\(L_{\text{air}}\)) | \(L_{\text{air}} = X_{\text{air}} / (2\pi f)\) (Winding Specific) | PSCAD Saturable Core / UMEC Modeling |
| Inrush Current Ratio (\(I_{\text{inrush}} / I_n\)) | 8.0 ~ 12.0 × Rated \(I_n\) (Decay \(\tau \approx 0.15\text{s} \sim 0.35\text{s}\)) | Protective Relay Coordination & POI Voltage Dip |
| Magnetizing Inrush Decay Constant (\(\tau\)) | \(\tau = L_{\text{air}} / R_w\) (Typically 100 ms – 350 ms) | Differential Relay (87T) Harmonic Restraint |
Need project-specific \(V\text{-}I\) curve or PSCAD `.csv` dataset for renewable grid interconnection?
Interactive V-I Calculator
2. 2D AutoCAD General Arrangement (GA) Drawing & Dimensional Profile
Figure 2.1 — 2D AutoCAD Dimensional Submittal Schematic
Dimensional & Installation Requirements
- Foundational Base: Steel channel Skid / Sub-station Pad Mounting.
- Bushings Orientation: HV top-mounted / side-cabinet entry option.
- Grounding Terminals: Dual M12 copper grounding pads on diagonal corners.
- Enclosure Protection: IP54 Outdoor Corrosive C4/C5 Marine Paint Coating.
- CAD Drawing File: Request `.DXF` or `.DWG` blocks from sales engineering.
3. Factory Acceptance Testing (FAT) & Routine Test Protocol
Every transformer manufactured by XinHuan undergoes 100% routine inspection in accordance with IEC 60076-1 before dispatch. Routine test certificates are included in the shipment package.
1. Winding Resistance Measurement (HV & LV)
2. Voltage Ratio & Vector Group Phase Displacement
3. Short-Circuit Impedance & Load Loss Test
4. No-Load Loss ($P_o$) & Excitation Current Test
5. Separate-Source AC Dielectric Withstand Test
6. Induced Overvoltage Withstand Test (DVWV)
7. Insulation Resistance & Polarization Index (Megger)
8. Hermetic Tank Pressure Leakage & Oil BDV Test
9. Extended Excitation Characteristic & Knee-Point Verification (to 120% \(V_n\))
10. Frequency Response Analysis (FRA) & Air-Core Reactance Test (Optional)
4. Seaport Logistics, Packaging & Warranty Terms
Export Packaging
IPPC fumigated solid wooden crate skid with vacuum moisture foil barrier.
Primary Delivery Ports
CIF Chancay, Callao, Apapa, Mombasa, Manila, Jakarta, Santos, & Valparaiso.
Factory Warranty
36 Months Full Replacement / Factory Engineering Warranty against defects.
Anhui XinHuan Electrical Power Equipment Co., Ltd.
Factory Address: Industrial Park, Hefei City, Anhui Province, China | Export Dept: [email protected]
Submittal Document Code: XH-SUB-2026-0482 — Confidential Technical Datasheet