Back to Product
Ref: XH-SUB-2026-0485
XINHUAN Submittal Package
Anhui XinHuan Electrical Power Equipment Co., Ltd. | Hefei Manufacturing Base
CNAS Test Certified | ISO 9001:2015 | ISO 14001:2015 Registered OEM
SUBMITTAL REF: XH-SUB-2026-0485
Date: 2026-10-30
Standard: IEC 60076 / GB/T 1094 / ANSI C57
Isolation Transformers

BK Industrial Machine Tool Control Transformer (25 VA – 5000 VA)

Submittal Specification Datasheet & Engineering Technical Parameters

1. Electrical Technical Parameters & Ratings

Parameter Specification Design Rating & Certified Value
Rated Capacity 25VA, 50VA, 100VA, 150VA, 250VA, 500VA, 1000VA, 2000VA, 5000VA
Primary Voltage 380V, 220V AC (Multi-tap input)
Secondary Voltage 36V, 24V, 12V, 6V AC
Frequency 50 Hz / 60 Hz
Installation DIN Rail or Base Plate Screw Mount
Model BK-25~50VA A: 56±0.5 mm, C: 53±2 mm, Bmax: 80 mm, Dmax: 74 mm, Emax: 85 mm, K×J: 4.8×9 mm
Model BK-100VA A: 64±0.5 mm, C: 65±2 mm, Bmax: 86 mm, Dmax: 84 mm, Emax: 92 mm, K×J: 4.8×9 mm
Model BK-150VA A: 84±0.5 mm, C: 80±2 mm, Bmax: 96 mm, Dmax: 97 mm, Emax: 110 mm, K×J: 5.8×11 mm
Model BK-200VA A: 84±0.5 mm, C: 87±2 mm, Bmax: 96 mm, Dmax: 105 mm, Emax: 110 mm, K×J: 5.8×11 mm
Model BK-250VA A: 84±0.5 mm, C: 90±2 mm, Bmax: 96 mm, Dmax: 110 mm, Emax: 110 mm, K×J: 5.8×11 mm
Model BK-300VA A: 90±0.5 mm, C: 98±2 mm, Bmax: 120 mm, Dmax: 120 mm, Emax: 125 mm, K×J: 7×13 mm
Model BK-400~500VA A: 90±0.5 mm, C: 104±2 mm, Bmax: 135 mm, Dmax: 128 mm, Emax: 125 mm, K×J: 7×13 mm
Model BK-700VA A: 110±0.5 mm, C: 97±2 mm, Bmax: 152 mm, Dmax: 125 mm, Emax: 147 mm, K×J: 7×13 mm
Model BK-1000VA A: 111±0.5 mm, C: 113±2 mm, Bmax: 170 mm, Dmax: 148 mm, Emax: 165 mm, K×J: 7×13 mm

Transient Simulation & Saturation Characteristics (PSCAD / ETAP / EMTP)

IEEE C57.12.00 / IEC 60076-1
Electromagnetic Parameter Design Characteristic & Certified Benchmark Grid Study Application
Saturation Knee-Point Voltage (\(V_k\)) 1.15 ~ 1.22 p.u. of \(V_n\) (CRGO Laser Core) Overvoltage & Ferroresonance Protection
Air-Core Reactance (\(X_{\text{air}}\)) \(2.0 \sim 2.5 \times X_{sc}\) (Standard: \(2.1 \times X_{sc}\)) Deep Saturation Inrush Peak Limit
Air-Core Inductance (\(L_{\text{air}}\)) \(L_{\text{air}} = X_{\text{air}} / (2\pi f)\) (Winding Specific) PSCAD Saturable Core / UMEC Modeling
Inrush Current Ratio (\(I_{\text{inrush}} / I_n\)) 8.0 ~ 12.0 × Rated \(I_n\) (Decay \(\tau \approx 0.15\text{s} \sim 0.35\text{s}\)) Protective Relay Coordination & POI Voltage Dip
Magnetizing Inrush Decay Constant (\(\tau\)) \(\tau = L_{\text{air}} / R_w\) (Typically 100 ms – 350 ms) Differential Relay (87T) Harmonic Restraint
Need project-specific \(V\text{-}I\) curve or PSCAD `.csv` dataset for renewable grid interconnection? Interactive V-I Calculator

2. 2D AutoCAD General Arrangement (GA) Drawing & Dimensional Profile

2D AutoCAD Blueprint
Figure 2.1 — 2D AutoCAD Dimensional Submittal Schematic

Dimensional & Installation Requirements

  • Foundational Base: Steel channel Skid / Sub-station Pad Mounting.
  • Bushings Orientation: HV top-mounted / side-cabinet entry option.
  • Grounding Terminals: Dual M12 copper grounding pads on diagonal corners.
  • Enclosure Protection: IP54 Outdoor Corrosive C4/C5 Marine Paint Coating.
  • CAD Drawing File: Request `.DXF` or `.DWG` blocks from sales engineering.

3. Factory Acceptance Testing (FAT) & Routine Test Protocol

Every transformer manufactured by XinHuan undergoes 100% routine inspection in accordance with IEC 60076-1 before dispatch. Routine test certificates are included in the shipment package.

1. Winding Resistance Measurement (HV & LV)
2. Voltage Ratio & Vector Group Phase Displacement
3. Short-Circuit Impedance & Load Loss Test
4. No-Load Loss ($P_o$) & Excitation Current Test
5. Separate-Source AC Dielectric Withstand Test
6. Induced Overvoltage Withstand Test (DVWV)
7. Insulation Resistance & Polarization Index (Megger)
8. Hermetic Tank Pressure Leakage & Oil BDV Test
9. Extended Excitation Characteristic & Knee-Point Verification (to 120% \(V_n\))
10. Frequency Response Analysis (FRA) & Air-Core Reactance Test (Optional)

4. Seaport Logistics, Packaging & Warranty Terms

Export Packaging
IPPC fumigated solid wooden crate skid with vacuum moisture foil barrier.
Primary Delivery Ports
CIF Chancay, Callao, Apapa, Mombasa, Manila, Jakarta, Santos, & Valparaiso.
Factory Warranty
36 Months Full Replacement / Factory Engineering Warranty against defects.
Anhui XinHuan Electrical Power Equipment Co., Ltd.
Factory Address: Industrial Park, Hefei City, Anhui Province, China | Export Dept: [email protected]
Submittal Document Code: XH-SUB-2026-0485 — Confidential Technical Datasheet