Electrical testing equipment — data center transformer sizing

Mühendislik Aracı

Data Center Sizing Calculator

Calculate required transformer capacity for mission-critical IT facilities based on active IT rack load, UPS conversion efficiency, CRAC/CRAH HVAC cooling, 2N/N+1 redundancy targets, and K-13 harmonic derating.

Yük Parametreleri

kW
kW

Please enter valid power values.

Sonuçlar burada görünecek

Enter your data center parameters and click Calculate

Calculated Load

kVA

Önerilen Boyut

kVA (Cast Resin)

Hesaplama Detayı

Suggested Transformer Type

Cast Resin Dry-Type Transformer (Class H 180°C)

F1 fire self-extinguishing safety, Pt100 RS485 thermal sensors, and K-13 harmonic protection.

Sonuçlar yalnızca ön tahmin içindir. Nihai seçim, proje özelliklerine ve mühendislik incelemesine göre onaylanmalıdır.

IEEE C57.110 Standard

S (kVA) = [ (P_IT / η_UPS) + P_HVAC + P_Aux ] / (PF × L_target × K_derate)

2N / N+1 Redundancy Ratio

Target operating load limit is 75% for 2N redundant systems, 80% for N+1.

Harmonic K-13 Rating

Protects transformer windings against non-linear server switch-mode power supplies.