Data Center Sizing Calculator
Calculate required transformer capacity for mission-critical IT facilities based on active IT rack load, UPS conversion efficiency, CRAC/CRAH HVAC cooling, 2N/N+1 redundancy targets, and K-13 harmonic derating.
معلمات الحمل
Please enter valid power values.
ستظهر النتائج هنا
Enter your data center parameters and click Calculate
Calculated Load
kVA
الحجم الموصى به
kVA (Cast Resin)
تفصيل الحساب
Suggested Transformer Type
Cast Resin Dry-Type Transformer (Class H 180°C)
F1 fire self-extinguishing safety, Pt100 RS485 thermal sensors, and K-13 harmonic protection.
النتائج هي لتقدير أولي فقط. يجب تأكيد الاختيار النهائي بناءً على مواصفات المشروع والمراجعة الهندسية.
IEEE C57.110 Standard
S (kVA) = [ (P_IT / η_UPS) + P_HVAC + P_Aux ] / (PF × L_target × K_derate)
2N / N+1 Redundancy Ratio
Target operating load limit is 75% for 2N redundant systems, 80% for N+1.
Harmonic K-13 Rating
Protects transformer windings against non-linear server switch-mode power supplies.