Calculate required transformer capacity for mission-critical IT facilities based on active IT rack load, UPS conversion efficiency, CRAC/CRAH HVAC cooling, 2N/N+1 redundancy targets, and K-13 harmonic derating.
Parameter Beban
Please enter valid power values.
Hasil akan muncul di sini
Enter your data center parameters and click Calculate
Calculated Load
kVA
Ukuran yang Direkomendasikan
kVA (Cast Resin)
Rincian Perhitungan
Suggested Transformer Type
Cast Resin Dry-Type Transformer (Class H 180°C)
F1 fire self-extinguishing safety, Pt100 RS485 thermal sensors, and K-13 harmonic protection.
Hasil hanya untuk perkiraan awal. Pemilihan akhir harus dikonfirmasi berdasarkan spesifikasi proyek dan tinjauan teknik.
IEEE C57.110 Standard
S (kVA) = [ (P_IT / η_UPS) + P_HVAC + P_Aux ] / (PF × L_target × K_derate)
2N / N+1 Redundancy Ratio
Target operating load limit is 75% for 2N redundant systems, 80% for N+1.
Harmonic K-13 Rating
Protects transformer windings against non-linear server switch-mode power supplies.