Data Center Sizing Calculator
Calculate required transformer capacity for mission-critical IT facilities based on active IT rack load, UPS conversion efficiency, CRAC/CRAH HVAC cooling, 2N/N+1 redundancy targets, and K-13 harmonic derating.
Vigezo vya Mzigo
Please enter valid power values.
Matokeo yataonekana hapa
Enter your data center parameters and click Calculate
Calculated Load
kVA
Ukubwa Uliopendekezwa
kVA (Cast Resin)
Uchanganuzi wa Hesabu
Suggested Transformer Type
Cast Resin Dry-Type Transformer (Class H 180°C)
F1 fire self-extinguishing safety, Pt100 RS485 thermal sensors, and K-13 harmonic protection.
Matokeo ni ya makadirio ya awali tu. Uchaguzi wa mwisho unapaswa kuthibitishwa kulingana na vipimo vya mradi na mapitio ya uhandisi.
IEEE C57.110 Standard
S (kVA) = [ (P_IT / η_UPS) + P_HVAC + P_Aux ] / (PF × L_target × K_derate)
2N / N+1 Redundancy Ratio
Target operating load limit is 75% for 2N redundant systems, 80% for N+1.
Harmonic K-13 Rating
Protects transformer windings against non-linear server switch-mode power supplies.