AREQUIPA REGION, PERU (ELEVATION 3,850M ASL) • ENGINEERING CASE STUDY
秘鲁安第斯铜矿5 MVA 33kV高海拔矿用变电站
定制高海拔工程 5 MVA 33kV 电力变压器,具有高爬电距离套管 (>31mm/kV)、降额冷却和 IP54 室外防护,适用于连续的安第斯铜矿开采作业。
1. 项目背景和运营挑战
High-altitude Andean mining operations (>3,500m ASL) experience severe atmospheric pressure drop and thin air dielectric insulation loss, high UV radiation, and wide ambient temperature fluctuations (ΔT = 45°C). Standard distribution transformers suffer severe thermal overheating and premature dielectric insulation breakdown when operated at altitude without specialized derating engineering.
2. 定制工程解决方案
XinHuan sales engineers designed a custom high-altitude 5000 kVA 33kV/0.48kV oil-immersed power transformer with expanded radiator cooling surface (+25% heat dissipation reserve), grain-oriented silicon steel core mitered step-lap miter joints to minimize no-load losses, high creepage distance porcelain bushings (>31mm/kV), and C5-M heavy industrial anti-corrosion marine paint.
3. 安装设备参数和额定值
| 参数规格 | 设计评级和认证值 |
|---|---|
| 额定容量 | 5000千伏安(5兆伏安) |
| 初级电压 | 33 kV (33,000V) |
| 二次电压 | 0.48 kV (480V 3-Phase) |
| Installation Elevation | 3,850 Meters Above Sea Level (ASL) |
| 冷却方式 | ONAN(天然油、天然空气) |
| 向量组 | Dyn11 |
| 短路阻抗 | 7.0% |
| 标准合规性 | IEC 60076-1 / ANSI C57.12 |
| 工厂保修 | 36 Months Manufacturer Warranty |
4. 项目成果和现场绩效
The 5 MVA unit was shipped direct to Port of Matarani & Callao, Peru. Commissioned in 2024, the transformer has operated continuously for over 18 months through peak copper crushing cycles with zero thermal trips and perfectly stable oil temperatures.
需要类似的技术提交吗?
我们的工程团队在 24 小时内提供 2D AutoCAD 总布置图、电气参数提交和 CIF 海港报价。